Technical Specifications :
Rated Output: Up to 7000 kVAr. (other powers are available)
Maximum Outlet Water Temperature : 40º C
Minimum Water Flow Rate: 4.5
liters/minute
Capacitance Tolerance: -5 +10
%
Working Voltages (Un): Any
voltages up to 3000 V AC
Working Frequency: 50 to 10.000
Hz. (other frequency available if requested)
Impregnating Fluid: Biodegradable and non-PCB
Installation: Indoor and suitable
for vertical or horizontal mounting.
Permitted Over Voltages: 1.05
Un 1 hour /day
Permitted Over Current (including harmonics but
excluding transients): 1.35 In
Switching Over Voltages (max: 10 ms): £2xÖ2 Un
Max. peak voltage (including harmonics): 1.65 Un
M14 Nuts of Terminals max. Torque: 10 N.m
Dielectric Losses (Tand -dissipation fact.):<0.15W/kVAr
Test Voltage Between Terminals: 2.15 Un AC,10 s
Test Voltage Between Terminals and Case: According to IEC 871-!/2 and TS standards.
Fuses: Not fitted. Available
upon request
Bushings: Steatite or wet process
Porcelain Bushings
Altitude: 2.000 m. (a.s.l)
Discharge Resistor: Not fitted. Available upon request
Reference Standards: Capacitors
meet or exceed of IEC 110-1/2; VDE0560-9(*); TS 3558 standards.
KONDAS Quality Assurance Standards: ISO 9002 Our Quality System is described in KONDAS Quality Manual.
|
|